VAV fan coil and demand controlled active chilled beam systems energy efficiency and thermal comfort performance comparison in a Japanese office building
1 Department of Civil Engineering, Aalto University, Espoo, Finland
2 Granlund Oy, Helsinki, Finland
3 School of Design and Architecture, Nagoya City University, Nagoya, Japan
4 Nagoya University, Nagoya, Japan
5 Tallinn University of Technology, Tallinn, Estonia
* Corresponding author: kaiser.ahmed@aalto.fi
In this study, we conducted a comprehensive analysis of indoor thermal condition, indoor air quality and energysaving potentials in a Japanese office building, comparing demand controlled VAV fan coil and active chilled beam (CB) room conditioning systems. The significant difference in these systems is whether or not to recirculate the conditioned air. The comparison was conducted with Osaka climate where cooling dominated over heating needs and higher summer humidity posed additional challenges. A typical Japanese office building was modeled in IDA-ICE for multizone operational performance assessment of studied systems. Also, primary side of heating and cooling system with air to water heat pump chiller was simulated using LCEM-tool ver. 3.01 to analyze HVAC energy consumption. Fan electricity was reduced with the implemented CB over existing fan coil system. These energy savings can be attributed to the difference in supply air volume and FCU installation. Both systems maintained indoor temperature and CO2 concentrations within the same limits, requiring fine-tuning of setpoints. CB operated with slightly higher relative humidity as it is less effective at dehumidifying the air, operating at non-condensing coil temperatures with dew point control. Overall seasonal coefficient of performance (SCOP calculated with PEF) was 1.37 for VAV system and 1.45 for CB system. The findings offer insights for sustainable HVAC systems, enhancing indoor air quality in offices.
Key words: VAV fan coil / Chilled beam / Energy efficiency / Indoor condition
© The Authors, published by EDP Sciences, 2024
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.