Numerical Simulation on the Heat Dissipation of the Outdoor Unit in the Groove of High-Rise Building
1
School of Aircraft Maintenance Engineering, Guangzhou Civil Aviation College, Guangzhou, 510403, China
2
School of Civil Engineering, Guangzhou University, Guangzhou, 510006, China
* Corresponding author: wangyuan_nuaa@163.com
In order to study the influence of the heat dissipation of the outdoor unit in the groove of the highrise building. Numerical simulation of the thermal environment of a high-rise building is carried out. The results show that: When the outdoor mean wind speed is 2.7m/s, the maximum inlet air temperature of the outdoor unit under full load condition is about 43.3 °C, which is 2 °C lower than that under no wind condition. The monsoon is beneficial to the heat dissipation of the outdoor unit. When the hot air in the building groove rises, the corner flow is induced at the lower side of the refuge layer. Due to the reverse pressure gradient, the flow separation occurs, resulting in the blockage in the flow channel. When the air flows through the refuge layer, the flow expands suddenly due to the increase of the cross-section of the channel. The turbulent boundary layer is separated. The vortex region is induced on the upper side of the refuge layer. Since the heat on the upper and lower sides of the refuge floor cannot be effectively dissipated, the inlet air temperature of the outdoor unit is higher than that of other floors, which reduces the working efficiency of the outdoor unit.
© The Authors, published by EDP Sciences, 2021
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.