Plenum airflow distribution and its influence on the performance of a diffuse ceiling ventilation
1 Department of Building Engineering, Energy Systems and Sustainability Science, University of Gävle, Kungsbäcksvagen 47, 801 76 Gävle, Sweden
2 SG Ecophon AB, Box 500, SE-265 03 Hyllinge, Sweden
* Corresponding author: alan.kabanshi@hig.se
Implementation of diffuse ceiling ventilation (DCV) is slowly gaining momentum and applications in building ventilation have taken off with countries like Denmark, Finland and Netherlands taking the lead in Europe. However, DCV is yet to gain a foothold in Sweden and so not many installations are known, and their performance in relation to Swedish building practice is not yet established. A school in southern Sweden was subsequently renovated and two classrooms were equipped with a sound-absorbent suspended ceiling compatible with DCV. DCV has possible benefits for educational environments including improved thermal comfort as well as lower costs and noise levels. However, it is currently still unknown how supply conditions in the plenum affect the diffusion of air and resulting conditions within the room. To assess airflow characteristics and whether these influence flow conditions in the classroom, we investigated and compared the performance of DCV with two different supply conditions in the plenum. Air speeds and temperature distribution measurements in the plenum and classroom were performed with constant temperature anemometers and thermocouples respectively. The general observation from this study and the system setup herein is that airflow and temperature characteristics in the classroom were independent of the airflow conditions in the plenum. Further investigations in a controlled climate chamber are recommended to investigate and optimise system performance in accordance with Swedish building practice.
© The Authors, published by EDP Sciences, 2022
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.