Ventilation effectiveness in classroom infection risk control
1 Department of Civil Engineering and Architecture, Tallinn University of Technology, Tallinn, Estonia
2 Department of Civil Engineering, Aalto University, Espoo, Finland
* Corresponding author: martin.kiil@taltech.ee
The benefits of a good ventilation in classrooms are a well-studied topic regarding health and learning outcomes. However, many studies still show poor results regarding air quality, air change rate and air velocities. In this paper, typical Estonian classroom air distribution solutions were studied in an air distribution laboratory at Tallinn University of Technology. The air change efficiency was measured with CO2 tracer gas concentration decay method. For determining the contaminant removal effectiveness, continuous dose method was used to create a constant contaminant source. In addition, by using air velocity probes, we conducted draught measurements in the mock-up classroom. Tests were conducted using dedicated room-based air handling unit and thermal mannequins for imitating heat sources from students. We found that all solutions studied ensured the air change efficiency roughly corresponding to fully mixing air distribution, but local ventilation effectiveness values of contaminant removal showed large variation from 0.6 to 1.7 stressing the impact of source location. Grouped ceiling supply circular diffusers and single vertical supply grille air distribution commonly used in renovated educational buildings resulted in higher draught risk on the border of the occupied zone. High air velocities recorded in some areas of the classroom perimeter, well explain why draught is considered as one of the main reasons why the airflow rates are reduced, or supply air temperatures are lifted compared to designed values. Perforated duct diffusers resulted in acceptable air velocities. In conclusion, local ventilation effectiveness of contaminant removal showed that fully mixing is not a case with a point source, although air change efficiency determined with equally distributed source showed fully mixing conditions. Therefore, in those cases, the air change rate should be increased to achieve the same ventilation effectiveness. Based on the experiments conducted, a point source ventilation effectiveness measurement method for the breathing zone is proposed. This value determined at least with two source locations can be used in infection risk-based ventilation design.
Key words: Classroom / ventilation effectiveness / air velocity
© The Authors, published by EDP Sciences, 2023
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.