Energy-saving potential of dedicated outdoor-air system assisted by vacuum-based membrane dehumidifier
Department of Architectural Engineering, Hanyang University, Republic of Korea.
* Corresponding author: jjwarc@hanyang.ac.kr
The proposed research presents a dedicated outdoor-air system (DOAS) integrated with a vacuumbased membrane dehumidifier (VMD). The primary objective of this study was to evaluate the energy-saving potential of the proposed VMD–DOAS combination. VMD–DOAS comprised a membrane-energy exchanger (MEE), dew-point indirect evaporative cooler (DP-IEC), and VMD. VMD possessed a characteristic by virtue of which the dehumidification process was isothermal; i.e., no temperature change was observed during the VMD process. While VMD served to control the dry-air supply, the required target temperature (i.e., 17 °C) was maintained via DP-IEC operation. The remaining sensible heat of the conditioned zone was controlled by the ceiling radiant cooling panel (CRCP). The load of the conditioned zone was driven by TRANSYS 18, and an engineering equation solver (EES) was used for evaluating the energy-saving potential of the proposed system with CRCP by comparing it against the variable-air-volume (VAV) system. Results of this study demonstrated that the proposed DOAS with CRCP consumed 37% less operating energy compared to the VAV system. This observed energy-saving potential of the proposed system was driven by reducing the dehumidification load and subsequent energy recovery by MEE.
© The Authors, published by EDP Sciences, 2019
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.