Effects on the Ventilation of a Two-Storey Building under Different Thermal Conditions
RWTH Aachen University, E.ON Energy Research Center, Institute for Energy Efficient Buildings and Indoor Climate, Germany
* Corresponding author: troeder@eonerc.rwth-aachen.de
In this paper it is shown how the air flow rate of decentralized ventilation devices can be affected by a staircase of a two-storey building under different thermal conditions. Since these devices need local fans for supplying the requested volume flow, pressure loads have a significant impact on the delivered volume flow rates. Regarding this, the study comprises two analyses: First, a CFD-model is developed to simulate the ventilation air flow through a simplified staircase. By varying parameters for rooms’ temperature and ventilation direction, the hydrostatic pressure in the staircase is evaluated. The simulations – characterized by high Archimedes numbers – are successfully validated with findings from preliminary work. In a second part, the pressure conditions inside the staircase are referred to outside conditions. Consequently, a static pressure difference at the ventilation device on each storey can be observed.
We found that the deliverable volume air flow rate can decrease up to 10 % from the nominal flow rate due to temperature differences between the storeys and outside. Therefore, heat recovery and ventilation effectiveness may also be impaired.
© The Authors, published by EDP Sciences, 2019
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.