Harmonic content of the synchronous generator stator current in the case of unit transformer saturation due to geomagnetically induced currents
1
Togliatti State University, 445020 Togliatti, Russia
* Corresponding author: tchernenko83@yandex.ru
The study investigates the features of the operation of off-the-grid power systems. Such power systems are commonly used for supplying power to consumers spread throughout the Arctic zone of the Russian Federation, and their unique operating conditions are due to the effect of geomagnetically induced currents (GICs) resulting from geomagnetic disturbances. We argue that the cause of stator current deviations from the pure sine wave are unit transformers. Their low-voltage windings are directly connected to stator windings of synchronous generators, and GICs run through grounded high-voltage windings. To support our claim, we simulated the effect of a test GIC event. Its amplitude in each of high-voltage phase windings of the unit transformer was 100 A, and the duration was 20 seconds (power transformers of the Hydro-Québec power grid were exposed to geomagnetically induced currents of a similar intensity during the geomagnetic storm on March 13-14, 1989). The spike targeted the "generator (TVF-100-2) - transformer (TDTs-125000/220/10.5)" unit that fed a major consumer node (Рnom = 83.125 MW, Qnom = 29.75 Mvar, cosφ=0.95) through a 160 km long double-circuit overhead line. Our study demonstrated that the effect of GICs on the operation of synchronous generators started from the moment of saturation of the unit transformer's core due to the inverse transformation of magnetizing current harmonics in the stator winding circuit. The harmonics introduced significant deviations from the pure sine wave into the curve of instantaneous stator currents. We calculated the nonlinear distortion factor of the stator current, which reached an unacceptably high value of THD=55.59%, 10 seconds into the test GIC event. The study showed that the 2nd and 4th harmonics of the unit transformer magnetizing current were responsible for the great bulk of deviations from the pure sine wave of the stator current.
© The Authors, published by EDP Sciences, 2023
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.