Measurements of thermal Transmittance of an External massive timber wall in-situ and in the Laboratory
Bern University of Applied Sciences, Solothurnstr. 102, CH-2500 Biel/Bienne, Switzerland
* Corresponding author: Christoph Geyer, Christoph.geyer@bfh.ch
The thermal transmittance of an exterior massive timber wall was measured in situ in Appenzell, Switzerland according to the standard ISO 9869-1. The measurements were performed with two different measurement sets in parallel. The measurements started in February and stopped at end of April. The measuring data were analyzed using mean values of the thermal transmittance coefficient and of the thermal resistance following the procedure of ISO 9869-1. In order to clarify if the in-situ measurement results show significant deviations from the measurement results of the thermal transmittance obtained in the laboratory, the thermal transmittance of the identical wall construction was measured in the laboratory of Bern University of Applied Sciences in Biel according to the standard EN ISO 8990 for steady state boundary conditions in a guarded and calibrated hot box. The test results will be presented and the measurement setup will be described. The calculation value of the thermal transmittance coefficient of the massive timber wall according to EN ISO 6946 is U = 0.53 W/(m2K). The test results of the thermal transmittance coefficient, U-value of the wall, measured in the hot box, agreed well within a confidence level of 95 % with the calculated value. The in-situ measurement results of the thermal transmittance coefficient of the two measurement sets differ significantly in the order of 8 % referred to the calculated U-value of the wall as the basic amount. Furthermore, both in situ test results of the U-value of the wall show significant deviations from the calculated U-value up to 27 %.
© The Authors, published by EDP Sciences, 2020
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.