Analysis of Backup Protection Action of a Transformer Caused by Improper Implementation of Voltage Regulation Measures
NARI Group Co., Ltd. (State Grid Electric Power Research Institute), Nanjing, China
* Corresponding author: chenyu2@sgepri.sgcc.com.cn
It is an effective measure for power enterprises to improve the voltage level of the system by raising and lowering the tap position of the main transformer. For the parallel operation of the main transformer, the whole process of adjusting the tap must strictly meet the conditions of parallel operation. Aiming at a case of backup protection action of main transformer caused by improper implementation of voltage regulation measures, this paper analyzes the uneven load distribution and increase of reactive power loss caused by improper adjustment of tap, and the analysis results are verified by PSCAD.
© The Authors, published by EDP Sciences, 2021
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.