Failure Analysis of the Guyed-V Tower Link Plate Deformation of a 500 kV Transmission Line
1 State Grid Hunan Electric Power Company Limited Research Institute, Changsha, Hunan, 410007, China
2 State Grid Changde Maintenance Company, Changde, Hunan, 415000, China
* Corresponding author’s e-mail: yjhu1@mail.buct.edu.cn
Component analysis, mechanical property test, field survey and finite element mechanical calculation were used to analyse and evaluate the deformation failure of the Guyed-V Tower link plate of a 500 kV transmission line. The results show that the main cause of the failure is the relaxation of the guy after right front guy or wire is subjected to a large impact towards the large side. The weak design of the link plate structure and the misfitting of angle steel are the indirect causes of the failure. The construction angle of anchor cable is larger than the design value, and the tension of anchor cable is low, which has a certain impact.
© The Authors, published by EDP Sciences, 2021
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.