A Novel Two-step Distance Protection for Flexible HVDC Transmission Lines
1 State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan, Hubei, 430074, China
2 State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan, Hubei, 430074, China
3 State Grid Jiangsu Electric Power Research Institute, Nanjing, Jiangsu, 210036, China
* Corresponding author’s e-mail: swenmh@hust.edu.cn
DC line fault is one of the key problems that must be solved in a flexible HVDC system. During quite a long time between the existing main protection and backup protection of the HVDC line, there is no line protection method to detect the fault, which may lead the protection at the AC side to act before the backup protection of the DC line. To solve the problem, a novel two-step distance protection for flexible HVDC lines is proposed in this manuscript. Firstly, based on the uniform distributed parameter model, the equivalent lumped parameter model of the HVDC transmission line at low frequency is analyzed. Secondly, according to the time domain differential equation and the least squares algorithm, novel distance protection based on the iterative calculation of fault distance is proposed, which can eliminate the influence of distributed capacitive current and improve the precision of calculation. To improve the rapidity and reliability of the distance protection, low pass filters with two different cut-off frequencies are used to process the electrical quantities. Finally, simulation results show that the proposed distance protection can respond to metallic poleto-ground faults and pole-to-pole faults rapidly and reliably.
© The Authors, published by EDP Sciences, 2021
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.