Issue |
E3S Web Conf.
Volume 356, 2022
The 16th ROOMVENT Conference (ROOMVENT 2022)
|
|
---|---|---|
Article Number | 05053 | |
Number of page(s) | 4 | |
Section | Indoor Air Quality and Airborne Contaminants | |
DOI | https://doi.org/10.1051/e3sconf/202235605053 | |
Published online | 31 August 2022 |
Control strategy of fan filter units in cleanroom considering of the moving personnel
1 Department of Building Science, Beijing Key Laboratory of Indoor Air Quality Evaluation and Control, Tsinghua University, China
2 Institute of Building Environment and Energy, China Academy of Building Research, China
* Corresponding author: xtingli@tsinghua.edu.cn
Fan filter units (FFUs) are crucial to maintaining the cleanliness of cleanrooms. Traditionally, the air volume of FFU is not adjusted and maintained at a rated value, resulting in a huge amount of energy. Previous research proved that controlling FFUs based on personnel position was effective in cleanrooms with the non-uniform environment, and could further reduce the air volumes. However, the control strategy for moving personnel has not been given. In this study, moving personnel is numerically simulated in a typical cleanroom. A control strategy is proposed that only the 4 FFUs above the personnel operate at high velocity and still operate at high velocity for 10 seconds after the personnel leaves. The results show that the control strategy can guarantee satisfactory cleanliness, and the air volume of the proposed strategy can be reduced by 53.6% and 18.7% compared with the uniform velocity strategies at designed velocity and decreased velocity, respectively. Since fewer and fewer personnel are in the cleanroom, the study will conduce to tremendous energy reductions of FFUs, which may have promising application potential in cleanrooms
© The Authors, published by EDP Sciences, 2022
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.