Field test of dehumidifiers for avoiding condensation in unheated historical wooden houses
1 Department of Building Engineering, Energy Systems and Sustainability Science, Faculty of Engineering and Sustainable Development, University of Gävle, SE-801 76 Gävle, Sweden
2 Department of Electrical Engineering, Mathematics and Science, Faculty of Engineering and Sustainable Development, University of Gävle, SE-801 76 Gävle, Sweden
* Corresponding author: magnus.mattsson@hig.se
The UNESCO world heritage “Decorated Farmhouses of Hälsingland” represent a well-preserved Swedish regional timber building tradition from the 18th and 19th centuries, featuring wall paintings of high cultural and artistic value. The houses have remained unheated and naturally ventilated over centuries, and have relatively leaky building envelopes. Recent indoor climate measurements and observations, however, have identified occasional condensation on indoor surfaces during unfavourable weather changes in wintertime. Such condensation poses a risk of degrading the wall paintings and other valuable objects, although low winter temperatures prevent mold growth. To mitigate condensation risk, sorption dehumidifiers – working also at temperatures below 0 °C – were installed in one of the UNESCO farmhouses during a winter season. The dehumidifiers were programmed to limit the indoor air relative humidity (RH) at maximum 80 %, and their dried air was distributed to all rooms via a flexible ductwork. Additionally, climate loggers and passive tracer gas technique were employed to measure temperature, RH, and air change rate in all rooms. By comparing with measured indoor climate in other similar farmhouses in the region, the results indicate that the dehumidifiers chiefly managed to limit RH at 80 %, thus preventing condensation in all rooms, despite a relatively high mean air change rate of around 0.8 ACH. However, locally and temporarily, enhanced RH peaks occurred, possibly due to unfavourable transient wind and/or stack conditions. The study also provides some practical installation guidance.
© The Authors, published by EDP Sciences, 2025
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.