Issue |
E3S Web Conf.
Volume 111, 2019
CLIMA 2019 Congress
|
|
---|---|---|
Article Number | 01037 | |
Number of page(s) | 5 | |
Section | Advanced HVAC&R&S Technology | |
DOI | https://doi.org/10.1051/e3sconf/201911101037 | |
Published online | 13 August 2019 |
Effect of Air Exchange Rate on Particle Decay in a Cleanroom: A Numerical Study
1 Karadeniz Technical University, Arsin Vocational School, 61900, Arsin Trabzon, Turkey
2 Karadeniz Technical University, Mechanical Engineering Department, 61080, Trabzon, Turkey
* Corresponding author: yecetin@ktu.edu.tr
In this study, particle decay in a cleanroom is investigated numerically. A commercial CFD package, FLUENT, is used in the analysis. The governing equations are solved by using the k-å turbulence model. For particle dispersion, the discrete phase model (DPM) is applied. Four different air change rates (3-10-25-43 ACH) with three particle diameters (0,5-5-10 ìm) are considered. It is shown that 10 ACH satisfies the needs in terms of recovery time.
© The Authors, published by EDP Sciences, 2019
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.