Measurement and Analysis of Evaporation in Indoor Swimming Pools: Comparison with the ASHRAE’s Activity Factor
1 COWI AS, Trondheim, Norway
2 SIAT NTNU - Centre for Sport Facilities and Technology, Norwegian University of Science and Technology, Department for Civil and Transport Engineering, Trondheim, Norway
3 Department of Energy and Process Engineering, Norwegian University of Science and Technology, Trondheim, Norway
* corresponding author: oosm@cowi.com
The evaporation rate from the swimming pool is a main parameter influencing the energy use in swimming facilities. Quantifying this phenomenon is crucial when modelling the facility in Building Performance Simulation. This study investigates the accuracy of ASHRAE equation using field measurements. This equation is widely used and implemented in BPS tools, such as the pool model in IDA ICE. The investigated dataset was based on two different indoor swimming pool facilities in Norway. It includes in total 75 swimming lessons (i.e., occupied pool) and 477 hours of unoccupied operation. While ASHRAE recommend 1.0/0.5 for occupied and unoccupied pools, respectively, the average activity factor was found to be 0.7 and 0.8 for the investigated occupied pools, with a maximum at 1.1. Moreover, the activity factor was between 0.50 and 0.57 for unoccupied pools.
© The Authors, published by EDP Sciences, 2022
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0 (http://creativecommons.org/licenses/by/4.0/).
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.