| Issue |
E3S Web Conf.
Volume 716, 2026
The 12th International Conference on Indoor Air Quality, Ventilation & Energy Conservation in Buildings (IAQVEC 2026)
|
|
|---|---|---|
| Article Number | 01055 | |
| Number of page(s) | 7 | |
| Section | Indoor Air Quality and Ventilation | |
| DOI | https://doi.org/10.1051/e3sconf/202671601055 | |
| Published online | 09 June 2026 | |
Ventilation Effectiveness in a Test Room: Experiments and CFD Validation
Hermann-Rietschel-Institut, Technische Universität Berlin, Marchstraße 4, 10587 Berlin, Germany
* Corresponding author: This email address is being protected from spambots. You need JavaScript enabled to view it.
Abstract
Abstract. Ventilation effectiveness is often interpreted under the assumption of fully mixed conditions, yet this assumption breaks down for localized emissions that dominate airborne-infection risk. This study presents controlled experimental and numerical evidence demonstrating how both exhaust placement and point source position strongly influence dilution performance in a mixing ventilated room. Full-scale measurements in a 5.2 m × 4.4 m × 2.85 m test space captured air velocities and CO2 tracer dynamics under different inlet-outlet layouts. These data were used to validate computational fluid dynamics (CFD) simulations, which then enabled assessment of additional source configurations. Agreement between CFD and measurements was generally satisfactory, with minor discrepancies attributable to idealized boundary conditions. The results show that changing the exhaust location fundamentally alters airflow organization, leading to pronounced differences in air-change efficiency and local air quality. While one configuration exhibited near-uniform dilution, the alternative layout promoted short-circuiting and strong sensitivity to source position, resulting in spatially nonuniform exposure conditions. These findings demonstrate that mixing ventilation does not inherently ensure homogeneous indoor air quality. The study provides a reproducible reference case for quantifying imperfect mixing under controlled conditions and establishes a foundation for future infection-risk-oriented evaluation and optimization of ventilation layouts.
Key words: Ventilation effectiveness / mixing ventilation / tracer gas measurements / CFD
© The Authors, published by EDP Sciences, 2026
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.